Abstract

It is important to monitor the moisture content of transformer oil in a transformer. One parameter of particular interest is the moisture solubility of transformer oil. It has been reported that transformer oils under different conditions have different solubility. Measurements of solubility for four different types of conditioned oil are presented in this paper: fresh Shell Diala AX oil, lab-aged Shell Diala A oil, Texas Utility used transformer oil, and Ramapo Substation used transformer oil. To avoid the difficulty of achieving full saturation, this paper proposes an alternative method of measuring the moisture solubility in transformer oil using a relative humidity sensor. It utilizes the linearity between the relative humidity of the oil and the moisture content of the oil, to measure the solubility indirectly. The measured results of fresh oil, lab-aged oil, and the Texas Utility oil are very close, and only Ramapo oil shows different sensor response characteristics and solubility.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.