Abstract

Current climatic projections show clearly that increasingly more extreme weather events are to be expected in the future. Historic buildings are considered to be the most vulnerable to this adverse climatic impact, via moisture induced deterioration and resulting strength decay in their construction materials. Therefore, the identification of these climatic effects is important to be able to develop suitable tools to mitigate them, both for individual buildings and on a regional scale. This paper presents the analysis of a comprehensive environmental monitoring of two historic buildings in Tewkesbury, Gloucestershire, UK, to provide thorough insight on their performances under environmental loading on a comparative basis. Firstly, the effect of wind-driven rain (WDR) and flooding is assessed by correlation with relative humidity (RH) measurements. The WDR measurements are then compared against values calculated using well established semi-empirical models and reasons behind the limited correlation are discussed. The dynamic hygrothermal response of two different historic fabrics is studied in greater detail by monitoring in-wall temperature and RH. The conclusions drawn from the analysis of the monitoring outputs are then further elaborated on by using hygrothermal characterization obtained by dynamic vapour sorption (DVS) testing of material samples extracted from the fabric of these buildings. The study concludes that the current environmental conditions pose a threat on the building envelopes unless routine maintenance is provided, and that monitoring methodology devised is clearly successful in quantifying the exposure of the two historic buildings to environmental conditions, onsetting deterioration phenomena in the envelop materials.

Highlights

  • Projections of current climatic events reveal compelling evidence that the overall precipitation has significantly risen e this increase is not always accompanied by a comparable increase in the number of wet days, extreme weather events are to be expected more intensely and more frequently in the future, globally and in the UK (e.g. Refs. [1e5])

  • When ISO model calculations are made using the wind values monitored on site, there is a significantly higher correlation between the calculated wind-driven rain (WDR) values and those measured on site

  • The historic buildings are known to be especially vulnerable to these actions and formulating correct measures able to counteract the adverse effect of climate on historic building envelopes requires a thorough understanding and an accurate quantification of the existing threat

Read more

Summary

Introduction

Projections of current climatic events reveal compelling evidence that the overall precipitation has significantly risen e this increase is not always accompanied by a comparable increase in the number of wet days, extreme weather events are to be expected more intensely and more frequently in the future, globally and in the UK (e.g. Refs. [1e5]). Tewkesbury is highly representative of a location with long history of exposure of its building stock to critical events and of future heightened hazards. The second building, 1-Mill Bank is a 16th century 2 storey oak timber frame cottage with brickwork infill, Grade II listed, located on raised ground on the bank of the River Avon, right across the road from the Abbey Mill. Both buildings whose use is currently residential, are known to have been in use throughout their lives and in a good state of conservation with functioning drainage and roofs and no visible structural distress

Environmental monitoring
Horizontal rainfall and wind-driven rain
Temperature and relative humidity
Possible adverse effects of moisture and temperature variations within walls
Findings
Conclusions