Abstract
The presence of moisture in oil impregnated paper insulation (OIP) is detrimental to its long time performance. Until recently, it was thought insulation ageing was only a function of temperature and electrical stress. It has now been realized that moisture in all its forms causes rapid degradation of the electrical and mechanical properties with time. In this study, insulation paper samples were conditioned for desired level of moisture and were impregnated with premium quality transformer oil. The oil impregnated samples with 1 to 3% moisture content were aged at 90 to 130°C. The indices for determining the extent of ageing considered in this work are degree of polymerization (DP), furan, carbon monoxide and carbon dioxide content. These quantities were monitored throughout the ageing experimental run. End-of-life (EOL) criterion used here is the reduction in the value of DP. Phenomenological models for estimating the service life of insulation are proposed and are validated against actual experimental data.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Dielectrics and Electrical Insulation
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.