Abstract

In a dc chopper converter having its load current regulated by a feedback controller of the fixed hysteresis type, the chopping frequency is shown to depend on the square of the counter EMF of the load. In a pulsewidth modulated (PWM) inverter, the counter EMF is modulated at the output frequency, so the chopping frequency is modulated at twice the output frequency. For a three-phase PWM inverter feeding a three-wire load, the chopping frequency modulation is not smooth. This is explained to be a consequence of the fact that the three phase currents must sum to zero, rendering one of the three current controllers redundant.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.