Abstract

The lightning surge analysis of an overhead line-underground CV cable transmission system has been carried out using the modified Fourier transform with a multiconductor representation. The frequency dependence of the transmission system components such as the overhead transmission line, underground cable and towers has been analyzed. A digital simulation based on this analysis has been developed and applied to a 77 kV three-phase single-circuit system. The results for a direct hit by a lightning stroke at the riser pole tower top show that the overvoltages at the riser pole increase with increase in the tower footing resistance and that the phase conductor overvoltages are greatly affected by the CV cable. The cable open-tie overvoltages decrease with increase in the cable length.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call