Abstract

Models to evaluate upper room ultraviolet germicidal irradiation (UVGI) devices can be used to improve the understanding of the behaviour of UV devices in ventilated rooms and so enable more confident predictions to be made of their performance. This paper presents two- and three-zone mixing models for investigating the effect of upper room UVGI devices in a typical ventilated room. The results from these analytical models are compared to a CFD simulation of the same room that incorporates the biological inactivation of micro-organisms in the presence of an ultraviolet field. The study demonstrates that analytical mixing models give reasonably good average zone concentrations and are therefore useful in estimating overall performance. However, the CFD simulations are necessary to fully examine the interaction of the room airflow with the inactivation of micro-organisms due to the UV field.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.