Abstract

In this work, low current discharges (less than 10 mA) are classified into two forms: unstable discharges and stable arcs. Such discharges may present on outdoor insulation surfaces due to the complex conditions created by the electrical fields, moisture and insulation geometry. The discharges can lead to heating and chemical effects; potentially degrading the insulation surface and accelerating further damage. Modeling of such discharges has been conducted, and a simulation including the test circuit arrangement for the various conditions has been created in the `PSCAD' software. The outcome of current and voltage curves from the simulation show good correlation with experimental data for the range of unstable discharges and stable arcs studied. The simulation work agrees with experiment work in that a low current discharge will become more detrimental if it is transformed from an unstable state to a stable arc, or if the stable arcs are physically compressed in length by any mechanism.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.