Abstract

Using a wind tunnel, a series of model finned flat tube copper radiators was studied. All geometrical parameters of the studied radiators were fixed except for the height of the fin, which was varied in the range from 5 to 20 mm. It was found that the global water-air heat transfer coefficient weakly depends on the water flow rate and significantly depends on the air flow rate. Correlations between the Nusselt and Reynolds numbers for fins with different heights are found. Based on the obtained correlations, a procedure for scaling the heat exchanger, verified experimentally, is proposed. The experiments performed demonstrate the efficiency and time-saving potential of the proposed method for choosing the optimal finned flat tube heat exchanger for adsorption heat conversion systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.