Abstract

There has been an unbalance between demand and supply of electricity in Maharashtra, a shortage of 20% peak power was reported in year 2011-12. Demand side management (DSM) in the commercial sector (consuming about 12% of the state electricity) can help to bridge this gap. In this paper three DSM options namely global temperature adjustment (GTA), chilled water storage (CWS) and variable air volume system (VAVS) are evaluated to give potential energy savings and load shifting. Simulation of GTA model for a sample school building gave 21.3% saving in compressor work for a change of room settings from 23oC, 50% RH to 26oC, 40% RH. Model for CWS was simulated for an office building in Mumbai; the results showed a cooling load shifting of 1638TRh out of 2075TRh was possible with an optimum tank size of 450kl. Simulation of VAVS for a sample school building showed fan energy savings of 68% over CAVS.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.