This paper proposes an active beam model suitable for building energy simulations with the programming language Modelica. The model encapsulates empirical equations derived by a novel active beam terminal unit that operates with low-temperature heating and high-temperature cooling systems. Measurements from a full-scale experiment are used to compare the thermal behavior of the active beam with the one predicted by simulations. The simulation results show that the model corresponds closely with the actual operation. The model predicts the outlet water temperature of the active beam with a maximum mean absolute error of 0.18 °C. In term of maximum mean absolute percentage error, simulation results differ by 0.9%. The methodology presented is general enough to be applied for modeling other active beam units.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.