Abstract

In this paper, a membrane heat pump is proposed and analyzed. Fundamentally, the proposed heat pump consists of an aqueous CaCl 2 solution flow separated from a water flow by a vapor-permeable membrane. The low activity of the solution results in a net flux of water vapor across the membrane, which heats the solution stream and cools the water stream. This mechanism upgrades water-side low-temperature heat to solution-side high-temperature heat, creating a “temperature lift.” The modeling results show that using two membranes and an air gap instead of a single membrane increases the temperature lift by 185%. The model predicts temperature lifts for the air-gap design of 24, 16, and 6 °C for inlet temperatures of 55, 35, and 15 °C, respectively. Membranes with lower thermal conductivities and higher porosities improve the performance of single-membrane designs while thinner membranes improve the performance of air-gap designs. This device can be used with a solar heating system which already uses concentrated salt solutions for liquid-desiccant cooling.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.