Abstract

As a part of a commissioning study, the chilled ceiling system of a large commercial building located in Belgium is evaluated. A representative office has been instrumented and data on the chilled ceiling system operating in real conditions have been collected. The simulation of the whole system is performed by means of a transient thermal model of the building and its HVAC system. The model considers the hydronic panels as a transient-state finned heat exchanger connected to a simplified lumped transient model of the building. The behavior of the hydronic ceiling system and the interactions with its environment (walls, ventilated facade, internal loads and ventilation system) has been experimentally and numerically evaluated. Commissioning test results show that the influence of surfaces temperatures inside the room, especially the facade, is considerable. Then, it is clear that the hydronic ceiling system must be evaluated together with its designed environment and not as a separate HVAC equipment.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.