Abstract

In electric distribution systems, a series arc occurs when a load and a power source are disconnected from a connector such as a circuit breaker, a socket–plug, or a coupler. In dc systems, the arc is not extinguished unless the arc current decreases to zero. Sustaining plasma arc current can cause huge fire disasters. To cope with the arc faults in dc systems, the characteristics of the arc should be analyzed. However, a clear analysis method has not been suggested. This paper analyzes characteristics of a series-breaking arc in a dc circuit breaker in three operation phases: initiation, sustenance, and extinguishment. Based on the three operation characteristics, a series-breaking arc model is proposed and evaluated through experiment.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.