Abstract

The use of capacitive dividers (CDs) in medium-voltage (MV) networks started as simple voltage detectors and as rough voltage measurement instruments for protective purposes. Now, with the spread of intelligent electronic devices and renewable energy sources at the distribution level, capacitive dividers are designed and installed to perform accurate voltage measurements. Such a requirement is mandatory when the power quality has to be assessed. Therefore, CDs are currently being used either for power frequency or for high-frequency (supraharmonic- or partial-discharge-level) measurements. In this paper, typical off-the-shelf CDs are studied and modeled to understand how they behave in a wide range of frequencies and when the temperature varies. To this purpose, specific setups and tests have been developed and performed. From the results, it is clear that with proper modeling of CDs, it is possible to exploit them for measuring phenomena in a wide range of frequencies, including the effects due to temperature variations and self-resonances.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.