Dynamic phasor model of modular multilevel converter based high-voltage DC transmission (MMC-HVDC) and its initialization in power system dynamics simulations are presented in this paper. In order to study the influences of MMC-HVDC on the power system dynamic behaviors, the MMC-HVDC models need to be integrated into the power system dynamics simulation. Then the models must be initialized based on power flow data. Firstly, the dynamic phasor model of MMC-HVDC considering the internal dynamic characteristics of the MMC and suitable for dynamics simulation of power system is proposed, and then it is initialized based on AC-DC power flow data. Finally, the influences of auxiliary frequency control of MMC-HVDC on the angle stability of the system are studied through the four-machine two-area system. The correctness of the dynamic phasor model is verified by comparison with electromagnetic transient simulation. And the dynamics simulation results show that the auxiliary frequency control of MMC-HVDC can improve the angle stability of the system.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.