Abstract
This paper analyzes the control strategy and the fault characteristics of the grid voltage asymmetry through theoretical analysis, establishment of fault control model, simulation verification and other methods. Based on the theoretical analysis, the fault recording of a wind farm in Jiangsu is analyzed. Since the voltage and current have the negative sequence component when the grid has asymmetrical fault, a dual decoupling current control model is established. In the model, the notch filter is used to filter the double frequency component in the current, and the phase angle of the voltage positive sequence component is measured by DSOGI-PLL. Research shows that a notch filter can effectively eliminate the double frequency component, but it will reduce the stability of the system. The DSOGI structure has low-pass filtering characteristics. The problem of oscillation of the instantaneous power injected into the grid can be solved by a control strategy.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.