Abstract

Modeling and Detection of Turn-to-Turn Faults in Shunt Reactors

Highlights

  • The shunt reactors are generally parallel connected at both sides of the long overhead transmission lines or pipe-type cables [1], [2]

  • As a result, using such an approach with a fictitious winding makes it possible to develop an equivalent circuit, representing the shunt reactor for any location of turn-to-turn fault with a small number of turns involved [15]

  • The estimated zero-sequence reactance allows to determine whether the fault is within the zone or out-of-zone with respect to the shunt reactor terminals; it works like a directional element

Read more

Summary

INTRODUCTION

The shunt reactors are generally parallel connected at both sides of the long overhead transmission lines or pipe-type cables [1], [2]. Three methods for detecting turn-to-turn faults based on zero-sequence reactance, negative-sequence reactance, and phase impedance are proposed They are very simple to implement and can be used for any type of shunt. The three-phase shunt reactor may be solidly grounded and directly connected to the line, or it may remain ungrounded and connected to a transformer tertiary winding (Fig. 1a, b) Both configurations were taken into account when analyzing turn-to-turn faults since the connection way affects the current fault level, symmetrical components flow, etc. As a result, using such an approach with a fictitious winding makes it possible to develop an equivalent circuit, representing the shunt reactor for any location of turn-to-turn fault with a small number of turns involved [15]. The resistance is comparable, or sometimes even much larger than the reactance [16], [17], [18]

ZK iZZ wK wZ
EZZ ZZZ
Zx in operating region
Number of shorted turns
TABLE VI
CONCLUSION
Findings
TABLE IX FINAL RECOMMENDATIONS
Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call