Abstract

This paper addresses ac microgrid stability under high penetration of converter-interfaced loads (CILs). According to the Nyquist admittance ratio criterion, destabilizing interaction dynamics are yielded among the interfacing voltage-source inverter (VSI) of the ac microgrid and CILs. Active stabilization techniques are proposed to maintain the overall system stability from the VSI side using admittance-based small signal analysis. Sensitivity and robustness analyses are presented to assess the dynamic coupling among active damping and voltage tracking controllers of the interfacing VSI. A complete Matlab/Simulink model of an ac microgrid with multiple CILs is used to demonstrate the effectiveness of the proposed active compensation techniques.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.