Abstract
This paper addresses ac microgrid stability under high penetration of converter-interfaced loads (CILs). According to the Nyquist admittance ratio criterion, destabilizing interaction dynamics are yielded among the interfacing voltage-source inverter (VSI) of the ac microgrid and CILs. Active stabilization techniques are proposed to maintain the overall system stability from the VSI side using admittance-based small signal analysis. Sensitivity and robustness analyses are presented to assess the dynamic coupling among active damping and voltage tracking controllers of the interfacing VSI. A complete Matlab/Simulink model of an ac microgrid with multiple CILs is used to demonstrate the effectiveness of the proposed active compensation techniques.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.