Abstract

This article presents a comparative simulation-based control logic design process. It uses the Control Description Language (CDL) and the ASHRAE Guideline 36 high-performing building control sequences with the Modelica Buildings Library (MBL) to demonstrate a comparative analysis of two control designs for a data center chilled water plant. Details include a description of the closed-loop plant and control design methodology, including sizing and parameterization, base and alternative (Guideline 36) control logic with software implementation structure, and outline of the simulation experimentation process. The selected control designs are paired with comparable chilled water plant configurations. The models include a chiller, a water-side economizer, and an evaporative cooling tower. The plant provides cooling at 27ºC zone supply air temperature to a data center in Sacramento, CA. The comparative simulation results examined the impacts of a selected control logic detail, and present an example model-based design application. Overall, the simulation results showed a 25% annual and a 18% summer energy use reduction for alternative controls. This shows that simulation-based control logic design performance evaluation can improve energy efficiency and resilience aspects of system controls at large.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.