Abstract

For weak grid scenario with high new energy proportion, large fluctuations of load are prone to cause low-voltage ride through. Moreover, stator transient magnetic flux will cause overvoltage and overcurrent problems in the rotor of doubly fed induction generator. Based on model predictive control, a control strategy for transient flux linkage and reactive power compensation is proposed. Firstly, regarding the issue of reactive power allocation of grid side converters (GSC) and rotor side converters (RSC), an allocation strategy is derived under minimizing winding energy loss on case of low-voltage ride through, enabling the wind energy conversion system to provide reactive power support during grid voltage recovery process. Meanwhile, an improved mixed second- and third-order generalized integrator (MSTOGI) phase-locked loop (PLL) is used to extract the positive and negative sequence components of the power grid voltage, further for RSC control. Secondly, in response to power grid faults, considering the influence of stator DC transient flux and negative sequence flux components on rotor current, by injecting rotor transient compensation current and stator flux feedforward compensation into RSC, the rotor impulse voltage and loop current are reduced. Moreover, combined with model predictive control algorithm, a control strategy of rotor current is designed. Finally, a simulation platform is built to validate the effectiveness of the proposed method based on comparing with several traditional vector control low-voltage ride through methods.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call