Abstract
This paper describes the transient performance and voltage regulation of a stand-alone self-excited induction generator (SEIG). All characteristics are calculated with a ftux-based mathematical model of the induction machine in the stationary reference frame appropriate for the stand-alone SEIG. The generator model and the control system model are developed using Matlab/Simulink. A presented generator model takes into account significant effects of magnetic saturation on the SEIG performance. The simulation was performed by loading the SEIG with a variable resistive load. Some of the computed characteristics are compared with experimental results. Both uncontrolled and controlled response of the SEIG to load variations were analyzed. It is shown that voltage variations can be reduced by using voltage source inverter and terminal voltage controller.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.