Abstract This paper proposes a model for calculating the total supply capability (TSC) for distribution system considering both feeder and substation transformer contingencies. Existing models and methods for TSC only consider substation transformer contingencies and ignore feeder contingencies. However, the feeder contingencies occur much more frequently than substation transformer contingencies in practice. Moreover, some operation state fail the feeder contingencies N − 1 verification even they pass the transformer contingencies N − 1 verification. In this paper, a TSC model is firstly proposed in which feeder and transformer N − 1 contingencies are fully considered. This model is designed in feeder level, which means the topology of interconnection among feeders is accurately modeled. Secondly, a supplementary model for load balancing is set up for a better load distribution solution on feeders and transformers at TSC loading. Finally, the method is tested in a test distribution system and a real partial distribution network and the results are verified by the traditional N − 1 simulation.