Abstract

Vacuum interrupters are required to perform a wide variety of roles within vacuum circuit breakers. One duty is to pass short-circuit currents with the vacuum interrupters' contacts closed for a period of time (1 to 4 seconds), after which the circuit breaker's mechanism must be able to open the contacts, Thus the possibility of contact welding must be minimized. The flow of current through practical contacts generates a repulsive blow-off force, which has to be balanced by a closing force from the circuit breaker mechanism plus the force from atmospheric pressure acting on the vacuum interrupter's bellows. The magnitude of the applied closing force is an important parameter in a vacuum circuit breaker's design. Axial magnetic field (AMF) vacuum interrupters have an additional attractive force because of the parallel currents flowing in the two AMF coils. This force is calculated using three-dimensional finite element analysis (FEA) for practical AMF designs using contact diameters ranging from 62-100 mm. These results are then compared to two dimensional FEA models and analytic formulas, including the effect of the current frequency on the results (DC vs. 50 Hz). These attractive forces can then be combined with the other forces acting on the closed vacuum interrupter contacts to calculate the threshold welding current: the current above which the contacts will form a weld. Calculations of the total closing force compare the difference in the threshold welding current between AMF and other VI contact designs.