Abstract

Low voltage switch disconnectors (SD) combine rated load switching with disconnector functionality, providing safe electrical isolation. Electrical contacts are separated forming an arc discharge that needs to be quenched at first current zero (CZ) to protect the load and the SD itself. With increased line voltage, interruption at first CZ crossing is getting more difficult due to increased transient recovery voltage (TRV) and larger post arc current, leading to excessive contact erosion with longer arcing time. Arc simulation methodology was utilized to improve the design for better arc cooling close to CZ. Therefore, benchmark values of arc resistance and thermal time constant were evaluated close to CZ for a successful test at lower line voltage. The cooling efficiency of different designs at higher line voltage was analyzed by 3D arc simulation. A revised design was able to clear overload currents at lower and higher line voltages at first CZ, preventing excessive contact damage.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.