Abstract
The paper presents a mathematical model describing the water temperature change in a buffer tank. The buffer tank is an integral part of modern greenhouse heating systems. The model includes heat fluxes from the heating boiler, heat fluxes transferred to the greenhouse interior and heat losses from the system (tank, pipes connecting the tank with the heating system). The differential method was used to determine the temperature value in the tank. Verification tests carried out in a real facility showed that the mean square error is 0.14K.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.