Abstract

Underdamped electromechanical oscillations (EMO), which are a typical problem of transmission systems, can also appear in power distribution systems (PDS) where synchronous generators are present. The tools to study EMO in bulk power systems are well established. Nevertheless, distributed synchronous generators have a different behavior from the ones connected to balanced three-phase bulk power systems. In these cases, some well-consolidated tools used to study EMO in bulk power systems are not adequate, since in distributed generation systems the load fluctuation is proportionally much higher and, therefore, it is not possible to define a good approximation for an equilibrium point. In this paper, a set of appropriate tools, which does not depend on the system model, is utilized to assess the presence of EMO in unbalanced PDS with synchronous generators. The obtained results show that the measurement-based methods which use ambient and ringdown responses can be applied to estimate the parameters of EMO in unbalanced PDS with high accuracy.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.