Abstract

This study presents a H ∞ mixed-sensitivity robust control design to improve the overall damping performance of low-frequency oscillations for power systems with doubly fed induction generator-based (DFIG) wind power generation. The supplementary damping controller is designed in the linear matrix inequality framework which allows the placement of the closed-loop poles inside a pre-defined region for improved stability. The damping signal is implemented at the reactive power modulation of the rotor-side converter of the DFIG wind turbine (DFIG-WT). The damping contribution of the power oscillator damper is compared with that provided by the power system stabiliser (PSS) of the synchronous generator (SG). State-space system analysis and time-domain simulations show the capability of DFIG-WT to enhance the overall damping of the oscillatory modes even if PSSs are not installed at SG s. Also, the designed controller shows a robust performance to wind speed variations. The performance evaluation is based on the revised two-area four machines system and the revised New England 39-bus system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.