Abstract
Stairwell pressurization systems should ensure a sufficiently high velocity at open doors between the stairwell and the fire floor without exerting large forces on closed doors in the stairwell. It appears, however, that strong winds may make it difficult, and many times impossible, to fulfill simultaneously these two requirements in tall buildings. A simple model is used for evaluating the possible use of different design parameters, such as the shape and size of the stairwell, the flow resistance of the exit path, the orientation of the exit door, relative to the direction of prevailing strong winds, additional lobbies, pressurization of the elevator shaft, and the type and location of the injection system, for mitigating the effect of winds on the performance of pressurization systems. Several examples are presented and compared. One novel finding is that the use of a helical stairwell configuration, which has a relatively low flow resistance, may drastically reduce adverse wind effects. Results of a 1:10 scale model study of flow in a helical stairwell are presented, which show that its resistance to flow resistance is approximately one quarter of that of convectional type stairwells.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.