Abstract
During the transient period at the start of a voltage sag, a DVR injection transformer can experience a flux-linkage that is up to twice its nominal steady-state value. In order to prevent the transformers from saturating it is normal to choose a rating flux that is double that of the steady-state limit. An alternative method is to limit the flux-linkage during the transient switch-on period, thus preventing saturation. It is shown through both simulation and experimental results that an adaptive form factor can be applied to the DVR injected voltage, which minimizes the disturbance seen by a sensitive load, while at the same time preventing saturation. The proposed method removes the need for rating the series injection transformers for the DVR transient switch-on period, and therefore removes the redundancy normally associated with their steady state operation. In economic terms, this may reduce the total cost of a DVR system, thus making it a more attractive solution for voltage sag mitigation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.