Abstract

Passing clouds can create unacceptable rapid voltage variations in weak distribution networks with a significant solar PV penetration. This paper investigates the benefit of a PV inverter ramp-rate control strategy using battery energy storage for the mitigation of rapid voltage variations. By controlling the discharging/charging operation of the energy storage appropriately, not only the inverter ramp-rate can be maintained at a desired level, but also the voltage variations can be controlled within acceptable limits. Results, from simulation using a real Australian distribution feeder with real load demand and PV output profile, show that with a high penetration of PV, the voltage variations can increase beyond the allowable limit stipulated by the IEC 61000-2-2 standards. However, with the proposed ramp-rate control, the variation can be maintained well below the limits.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.