This paper present three methods for tracking the fundamental frequency of power systems in digital protection relaying, which is based on numerical differentiation, hardware and digital filtering respectively. The numerical differentiation method is adaptive only to pure sinusoidal cases, and hardware and digital filtering method is used not only for pure sinusoidal cases but also non-sinusoidal cases. The numerical differentiation method is characteristic of high accuracy, lesser time and computation. The hardware and digital filtering method employs hardware and digital filter to decompose the fundamental component out of the non-sinusoidal signals, and then uses numerical differentiation algorithm to track the fundamental frequency.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.