Abstract
This paper presents a microprocessor based differential protection scheme for a single phase transformer with harmonic restraint feature to avoid mal-operation during inrush current conditions. The protection scheme is implemented by means of a single microprocessor of intel's 8088 type. The relay has been tested satisfactorily by an arranged circuit for differential protection of a test transformer in the laboratory for the above condition. The test results indicate that the relay detects the inrush or other abnormal conditions satisfactorily within an overall time of about 26 μs.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.