Abstract

Oil cooled power transformer has important role in the electricity distribution system. Its windings were immersed in oil as an insulating medium and also as a cooler. This oil would be heated up due to several things, the most significant was heat generated by winding’s power loss. The monitoring of oil temperature on the transformer was always done routinely every day to maintain its performance and health condition. IoT based measurements could improved efficiency and minimized manpower resources. To realize this the indirect non-destructive measurement method was proposed to estimate transformator’s temperature oil. It will corellate the oil temperature and body temperature through a constant calibration factor derived from calculations. Conducted experiment applied to specific existing transformator and followed by calculations resulted a calibration factor = 1.7749. The smallest average of estimated temperature error was lied in the range of 40 - 90 degrees Celcius.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.