Abstract

A methodology for evaluation of natural draft cooling tower (CT) performance and its application is presented. The study establishes the connection between CT performance and power output. It can estimate a change in a CT’s efficiency as well as an increase in power output as a function of cooling water temperature and load to the plant. The methodology consists of three subparts, i.e. Cooling Tower Profiler (CTP) method, CT model and a model of the power plant that are described in the first part of the paper. The second part focuses on application of the methodology in a way that minimizes error of the CT model. One week of data from the power plant were acquired for the analysis. In the CT a small area with irregularities was examined, and increased efficiency and power output are estimated by the methodology. Furthermore, another aspect of solving Poppe equations is examined resulting in reduced computational effort by approximately a half without losing any computational accuracy.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.