Abstract
This paper addresses the control of multiterminal voltage-source converters at high-voltage direct current in the context of offshore wind farms. Droop control is commonly used to regulate the dc voltage in this kind of grid, and droop parameters are selected on the basis of steady-state analyses. Here, a control design methodology is proposed based on the frequency-response analysis. This methodology provides a criterion to select the droop gains, taking into account the performance specifications [i.e., the desired voltage errors and the maximum control inputs (currents)]. The application of the methodology is illustrated with a four-terminal grid.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.