In order to quickly suppress voltage fluctuations at the point of common coupling (PCC) caused by the doubly fed induction generator, a closed‐loop control method of the static synchronous compensator (STATCOM) is proposed, through which proportional integral (PI) parameters of the current inner loop can be adjusted online. The core aim is to derive quantitative relationships between the PI parameters and the output current of the STATCOM based on combining mathematical mechanization theory (MMT) with digital signal processing. Due to the reduction and quasidivision of the MMT, this original control method can be used to adjust the PI parameters of the STATCOM online according to the actual sampling voltage and sampling current data. The simulation and experimental results show that this control method can make a quick PCC voltage recovery within 10 ms, which satisfies the Chinese standard GB/T‐14549‐93. It can provide a solution for large‐scale wind power curtailment that should be solved imperatively. © 2019 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEJ Transactions on Electrical and Electronic Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.