Abstract

When large scales DG are connected to the distribution system of unidirectional power currents, bi-directional power currents are formed, making it impossible to use conventional overcurrent protection methods alone to detect and isolate fault sections for ground and short-circuit faults. To solve these problems, this study proposed the method of protection against single-line-ground fault of common neutral line multi-contact local power distribution system using distance relay and directional relay. The proposed protection method was applied to the common neutral multi-ground distribution system to validate the protection against single-line-ground fault through the PSCAD/EMTDC software package and effectively detect and isolate only the zone of single-line-ground fault without malfunctions.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.