Abstract

This paper describes a method for the online measurement of an optical current transformer (OCT) onsite errors comparing with a conventional electromagnetic current transformer (CT) as the reference transformer. The OCT under measurement is connected in series with the reference electromagnetic CT in the same line bay. The secondary output signals of the OCT and the electromagnetic CT are simultaneously collected and processed using a digital signal processing technique. The tests developed on a prototype clearly indicate that the method is very suitable for measuring errors of the OCT onsite without an interruption in the service. The onsite error characteristics of the OCT are analyzed, as well as the stability and repeatability.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.