Abstract

AbstractThe paper discusses how current and voltage measurements derived from the substation can be used for single‐phase‐to‐ground fault location in medium‐voltage distribution lines. The networks considered are assumed to be radially operated with either an isolated or compensated neutral. In these networks the fundamental frequency ground fault currents usually are so small that no reasonable fault‐distance estimate can be based on them. A possible solution is the utilisation of ground‐fault initial transients. In this paper a method for ground‐fault distance estimation, based on the least squares estimation of transient parameters, is presented.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.