Abstract
Different from voltage-source converter (VSC), reactive power absorption of line-commutated converters (LCCs) changes depending on DC voltage level. Therefore, the amount of AC voltage fluctuations at inverter side are different according to $I$ – $V$ droop constants in hybrid multi-terminal high-voltage direct current (MT-HVDC) system. This paper proposes a method for calculating the $I$ – $V$ droop constants in a hybrid MT-HVDC system to suppress these AC voltage fluctuations, based on the sensitivity of AC and DC networks. Simulations performed using PSCAD demonstrate the effectiveness of the proposed method.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.