Abstract

Abstract Over a six-week period, eleven tests were performed at the U.S. EPA Incineration Research Facility (IRF) in Jefferson, Arkansas to evaluate the fate of trace metals fed to a rotary kiln incinerator equipped with a Calvert Flux-Forcer/Condensation Scrubber pilot plant as the primary air pollution control system (APCS). Test variables were kiln temperature, ranging from 538 °C to 927 °C; waste feed chlorine content, ranging from 0% to 3.4%; and scrubber pressure drop, ranging from 8.2 kPa to 16.9 kPa. Mercury was among the six hazardous constituent trace metals fed to the IRF’s pilotscale rotary kiln incineration system as part of a synthetic waste feed. This paper focuses on the test results solely with respect to mercury. As expected, mercury behaved as a very volatile metal throughout the tests; it was not detected in any kiln ash samples. Scrubber collection efficiency for mercury ranged from 67% to >99%, averaging 87%; this was somewhat lower than expected and may be attributable to low scrubb...

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.