Abstract
This paper is focused on the possibility of employing narrow band power line communication (PLC) in medium voltage (MV) distribution networks. The topic is investigated by means of both simulations and experimental tests, which were carried out in the distribution network of Ustica Island. In detail, a two-way MV communication was tested between two secondary substations connected by an MV cable power line. Each substation has a by-pass connection at MV bus-bars and an MV/LV oil filled power transformer. In this paper, the MV and the PLC systems under test are described and the experimental tests are presented, which were carried out to evaluate the parameters of the simulation model. The aforesaid model is described and a comparison is shown between simulation and results of experiments, which were carried out in the presence of voltage net, i.e., 24 kV. Finally, the possibility is investigated of a reliable communication and the faster achievable bit-rate; the analysis is performed by means of further experimental results of several communication tests, which were carried out with different modulation techniques.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Instrumentation and Measurement
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.