Abstract
This paper describes the design and implementation of the first medium-voltage impedance measurement unit (IMU) capable of characterizing in situ source and load impedances of dc and ac networks (4160 V ac, 6000 V dc, 300 A, 2.2 MVA) in the frequency range of 0.1 Hz–1 kHz. The IMU comprises three power electronics building blocks (PEBBs), each built using 10-kV SiC MOSFET H-bridges. The modularity of the PEBBs allows for both series and shunt perturbation injection modes to be realized, as both injection modes are needed to accurately predict the stability of the electrical system. The effectiveness of the proposed impedance identification approach is experimentally verified on medium voltage power grid.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.