Abstract

During the middle period of heating in winter, the author studied the characteristics of thermal comfort and thermal adaptation of 4 dormitories of a college in the west. At the same time, a questionnaire on subjective thermal sensation was conducted, and 500 questionnaires were distributed to the subjects. Finally, 462 valid questionnaires were obtained.Through the study of data, the function of real average thermal sensation and indoor operating temperature has been obtained. The results show that the thermal neutral temperature is 19.8 degrees, the male and female thermal neutral temperatures are 19.5 and 20.1 degrees respectively, and the acceptable ranges of 80% and 90% for males are 16.5℃—23.0℃、17.7℃—21.3℃.The acceptable range of 80% and 90% for females is 16.2℃—24.0℃,17.8℃—22.4℃ .

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.