Abstract

AbstractIn Kyushu Electric Power's 6.6‐kV distribution system, after a single‐phase ground fault occurred in the circuit of a distribution line, we experienced a phenomenon in which the analogue ground directional relays of the other circuits linked to the same bank were simultaneously tripped. In this paper, focus is placed on the mechanism and possibility of simultaneous tripping of ground directional relays. This mechanism was examined in an experiment carried out using an analogue simulator. The results of the test revealed that such simultaneous tripping was attributable to the neutral instability phenomenon of grounding potential transformers installed in an isolated neutral system. © 2010 Wiley Periodicals, Inc. Electr Eng Jpn, 171(2): 23–30, 2010; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.20919

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.