Abstract

In the neutral point ungrounded power distribution system, due to the nonlinear characteristics of the electromagnetic voltage transformer (PT) excitation inductance, ferromagnetic resonance overvoltage is easily generated under certain conditions, which seriously affects the safe operation of the system. This paper takes the Yecheng substation 6 kV distribution network as the model, and uses ATP-EMPT electromagnetic transient calculation software to theoretically analyze the characteristics and mechanism of ferromagnetic resonance caused by electromagnetic voltage transformer, and points out the main problems of ferromagnetic resonance in PT operation. This article discussed the existing harmonic elimination measures, proposed some effective suppression schemes and demonstrated the effectiveness of some mainstream harmonic elimination methods. The author’s work can provide a good reference for the prevention and control of ferromagnetic resonance overvoltage, and it also has high practical value for improving the power supply safety and reliability of the distribution network.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.