Abstract
Mechanical parameters are regarded as important content of high voltage vacuum circuit breaker's (HV-VCB) condition monitoring, and the location of closing and separating moment is the premise and key for these parameters' calculation. An on-line monitoring system based on FPGA+ARM+SBC for HV-VCB is designed and developed with various functions. On the basis of which, a new singular point detection method based on ensemble empirical mode decomposition (EEMD) is proposed and applied to mechanical parameters' calculation. Displacement signals are collected by on-line monitoring system firstly. Then, EEMD is adopted to decompose displacement signal into several intrinsic mode functions (IMF) which can eliminate interference. Afterwards, singular point is extracted which is regarded as the closing moment. Finally, mechanical parameters can be calculated. This method has been applied to analyze and process displacement signals of HV-VCB which type is VMB5–12. The calculation results of the experiments are much more precise. Satisfactory performance of on-line monitoring system and calculation method for mechanical parameters are certified by experimental results.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.