Abstract
The fan pressurization method for measuring air leakage through the building envelope relies on the assumption that the extraneous air leakage (EAL) through paths other than those through the specimen being tested is negligible. When EAL does exist, the calibration procedure by ASTM Standard E-283 is used to measure EAL values by covering the specimen or guarded chambers are used to equalize the pressure differences across these unintended paths. A new testing method, the flexible double-chamber method, is presented in this paper for large specimens where the above two approaches are difficult to implement and where flexible chambers are more easily applied. The experimental procedure and data processing routine are presented for the case of a full-size metal curtain wall specimen. The EAL is estimated by regression analysis in data processing. Inference analysis, multivariate error analysis, and the Monte Carlo simulation technique are also presented to examine the estimation errors.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.