Abstract

A large-scale experiment was performed to measure heat transfer to a massive cylindrical calorimeter engulfed in a 30 minute circular-pool fire. This test simulated the conditions of a truck-sized nuclear waste transport package in a severe fire. The calorimeter inner surface temperature and the flame environment emissive power were measured at several locations as functions of time. An inverse heat conduction technique was used to estimate the net heat flux to the calorimeter. Tall porous fences surrounded the test facility to reduce the effect of wind on the fire. Outside the fences, 2.9 m/s winds blew across the calorimeter axis at the beginning of the test but decreased with time. The wind tilted and moved the fire so that the initial flame environment emissive power was substantially less on the windward side than the leeward side. The calorimeter became more uniformly engulfed as the winds decreased. The maximum heat flux to the calorimeter was 150 MW/m2 on the leeward side at the beginning of the fire, and generally decreased with time. The local variations of calorimeter temperature and heat flux were closely related to the local flame environment emissive power.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.