Abstract

This paper describes the measurements of the air change rates and air flow patterns in two large single-cell aircraft hangar buildings. The decay of the tracer gas sulfur hexafluoride was used to measure the air change rates. It was possible to achieve a uniform mixture of indoor air and the tracer gas in the hangars using the air circulation fans of the heating system. Stratified air layers characterized the air flow patterns within the hangars. For the test conditions, measured air change rates for the two hangars are in the range 0.32 to 0.47 air changes per hour. Results also suggest that five sampling locations at about 1.8 m (6 ft) height are sufficient to obtain a representative air change rate for large single-cell buildings.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.